Troubleshooting by Error Code
SiUS342303E
369
Part 6 Service Diagnosis
3.74 Climate Talk Communication System Combination Error
(Before Initial Setting for Communication Completes)
Applicable
Models
CXTQ-TA
Error Code
UH-05
Method of Error
Detection
Detects the type of the devices constituted in Climate Talk Communication.
Error Decision
Conditions
The error decision is made when any of the following conditions is established before elapsing 4
minutes after the power is turned ON.
Two or more gas furnaces are detected.
Any unit other than the gas furnace is detected.
The initial setting for communication does not complete.
Supposed
Causes
Connection of wrong devices
The power of the gas furnace is not turned ON, or the power of the gas furnace is turned ON
after a certain period of time has been elapsed after the power of the CXTQ-TA was turned ON.
Disconnection of the communication wire between the CXTQ-TA and the gas furnace
Two or more gas furnaces are connected to one CXTQ-TA.
No gas furnace is connected.
Troubleshooting
YES
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
The gas
furnace and the
CXTQ-TA are turned O
N
at the same
time.
YES
YES
N
O
N
O
N
O
1 and 2
terminals of the
gas furnace and the
CXTQ-TA are
connected each
other.
Replace the CXTQ-TA PCB
or the gas furnace PCB.
Turn O
N
the gas furnace
and the CXTQ-TA at the
same time.
Connect the gas furnace of
proper combination. Do not
connect any other devices.
Ensure correct
w
iring of the
communication
w
ire
bet
w
een terminals.
Any
device other
than the gas
furnace of proper
combination is connected
to 1 and 2
terminals of
X
8
A.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...