background image

PILOT

Installation, use and maintenance manual

V 3.0

24/04/2022

EN

Содержание PILOT

Страница 1: ...PILOT Installation use and maintenance manual V 3 0 24 04 2022 EN...

Страница 2: ...tec srl The information contained in this document may be changed without notice Nastec srl Via della Tecnica 8 36048 Barbarano Mossano Vicenza Italy Tel 39 0444 886289 Fax 39 0444 776099 info nastec...

Страница 3: ...5 3 Cables entry 11 6 Mechanical installation 11 6 1 Installation environment 11 6 2 Cooling 12 6 3 Wall installation 12 7 Electrical installation 13 7 1 Grounding 13 7 2 Connecting cables 13 7 2 1 Po...

Страница 4: ...device that protects and controls single phase and three phase pumps by signaling Overcurrent phase failure excessive number of restarts The back lit LCD display allows viewing the absorbed current v...

Страница 5: ...n damage to the product the system in which it is installed and in the worst cases damage to property or persons with even fatal consequences WARNING Failure to comply with the instructions may lead t...

Страница 6: ...tions This may result in serious mechanical and electrical danger to the operator who upon seeing the device stopped may have intervened on it on the load or on the system in which it is installed DAN...

Страница 7: ...12 months Verify the maintenance of the protection rating ingress of dust or water by checking the tightening of the screws in the mechanical closing parts the gaskets and the cable glands Every 12 m...

Страница 8: ...If the warranty is applicable Nastec will repair the device Nastec is willing to refurbish the product upon offer In the absence of a warranty Nastec will make an offer to repair and or refurbish the...

Страница 9: ...posal of the product is subject to severe administrative and or criminal penalties 4 Transport and storage 4 1 Transport Avoid subjecting the product to severe shocks or extreme weather conditions dur...

Страница 10: ...r it has been used it is advisable to contact the manufacturer for further information on storage TIP For more information contact the dealer or technical support at service nastec eu or by opening a...

Страница 11: ...330 3x230V 2 4 PILOT 312 3x400V 2 2 PILOT 325 3x400V 2 4 PILOT 330 3x400V 2 4 PILOT 312 3x460V 2 2 PILOT 325 3x460V 2 4 PILOT 330 3x460V 2 4 5 3 Cables entry Cable gland Tightening torque Nm Cable dia...

Страница 12: ...over or with the cable glands open even if not connected to the power supply The infiltration of dust water or humidity may irreparably damage the device 6 2 Cooling The device is cooled by natural ve...

Страница 13: ...the latter is greater than 35 mm2 1 AWG 7 2 Connecting cables WARNING The connecting cables must comply with local regulations feature the appropriate cross section and meet the requirements for volta...

Страница 14: ...such as fuses and circuit break ers upstream of the device These trigger in the event of failure of a component inside the device Supply voltage Model Recommended fuse gC Recommended circuit breaker...

Страница 15: ...2 50 Fork for M4 screw P E 50 Fork for M4 screw Motor MOTOR AUX 50 Fork for M4 screw MAIN 50 Fork for M4 screw COM 50 Fork for M4 screw P E 50 Fork for M4 screw Running capaci tor RUN CAP FM3 6 3 x 0...

Страница 16: ...A2 14 A mm Pre insulated cable lug Stripping diagram Power Supply LINE L1 50 Fork for M4 screw A L2 50 Fork for M4 screw L3 50 Fork for M4 screw P E 50 Fork for M4 screw Motor MOTOR T1 60 Fork for M4...

Страница 17: ...otor start and stop Programmable as Normally Open or Normally Closed Relay outputs NO2 Normally Open ALARM relay NO2 COM2 closed contact without alarm NC2 COM2 closed contact with alarm or without pow...

Страница 18: ...0 37 0 55 53 6 4 AVIATOR 2 0 75 1 1 108 130 AVIATOR 3 1 5 2 2 1 8 9 2 27 Procedure for installing the board AVIATOR 1 Make the power connections relative to the power supply the motor and the run cap...

Страница 19: ...female faston terminals of board AVIATOR in the male faston terminals of board PILOT paying attention to the correct insertion of all 4 terminals 5 Gently press the board AVIATOR downwards making sure...

Страница 20: ...otor cable paying particular attention to any connection reversal Check the correct connection of the power and signal cables paying particular attention to any polarity Check that the connection term...

Страница 21: ...s perform programming start the motor 9 Use and programming 9 1 Keyboard and display 1 2 3 4 5 6 1 DISPLAY 2 START motor start 3 STOP motor stop alarm reset exit the menu 4 ENTER access the menu edit...

Страница 22: ...e device intervenes by stopping the pump It corresponds to the rated motor current increased by 10 Dry run PF Minimum power factor or cos below which the device intervenes by stopping the pump The dry...

Страница 23: ...current in the COM MON phase of the sin gle phase motor or on the T1 phase of the three phase motor Check that the load is correctly connected Check the load and the connection WATER MISSING The warni...

Страница 24: ...easured cosphi value on the display or on the App Parameter Dry run PF must therefore be set to 10 less than the cosphi value read under closed flow condition CAUTION The electronic water shortage pro...

Страница 25: ...ectives 2011 65 EU RoHS Directive 2014 35 EU Low Voltage Directive LVD 2014 30 EU EMC Directive 2006 42 EC Machinery Directive MD and that the following harmonized standards and technical specificatio...

Страница 26: ...pment Regulations 2012 RoHS2 UK SI 2016 No 1101 The Electrical Equipment Safety Regulations 2016 UK SI 2016 No 1091 Electromagnetic Compatibility Regulations 2016 UK SI 2008 No 1597 The Supply of Mach...

Страница 27: ......

Страница 28: ......

Отзывы: