Field Setting from Outdoor Unit
SiUS342303E
215
Part 5 Field Settings and Test Operation
2.6 Energy Saving and Optimum Operation
This
VRV
system is equipped with advanced energy saving functionality (VRT). Detecting all
connected indoor unit type, advanced energy saving functionality type is selected automatically.
Depending on the priority, emphasizes can be put on energy saving or comfort level. Several
parameters can be selected, resulting in the optimal balance between energy consumption and
comfort for the particular application.
Several patterns are available and explained below.
Modify the parameters to the needs of your building and to realize the best balance between
energy consumption and comfort.
2.6.1 Target Temperature Settings
• Basic
The refrigerant temperature is fixed independent from the situation.
It corresponds to the standard operation which is known and can be expected from/under previous
VRV
systems:
To activate this operation method under cooling operation: Change field setting [2-23] to 1 or
disconnect the circuit between terminal on external control adaptor with [2-11]
≠
0.
To activate this operation method under heating operation: Change field setting [2-23] to 2 or
disconnect the circuit between terminal on external control adaptor with [2-11]
≠
0.
• Automatic for VRT control
The refrigerant temperature is set depending on the outdoor air conditions. As such adjusting the
refrigerant temperature to match the required load (which is also related to the outdoor air
conditions).
E.g., when your system is operating in cooling, you do not need as much cooling under low outdoor
air temperatures (e.g., 77°F (25°C)) as under high outdoor air temperatures (e.g., 95°F (35°C)).
Using this idea, the system automatically starts increasing its refrigerant temperature, automatically
reducing the delivered capacity and increasing the system’s efficiency.
This operation is selected automatically with checking connected indoor unit type.
E.g., when your system is operating in heating, you do not need as much heating under high
outdoor air temperatures (e.g., 68°F (20°C)) as under low outdoor air temperatures (e.g., 23°F
(–5°C)).
Using this idea, the system automatically starts decreasing its refrigerant temperature,
automatically reducing the delivered capacity and increasing the system’s efficiency.
This operation is selected automatically with checking connected indoor unit type.
• Hi-sensible
The refrigerant temperature is set higher/lower (cooling/heating) compared to basic operation. The
focus under high sensible mode is comfort feeling for the customer.
The selection method of indoor units is important and has to be considered as the available
capacity is not the same as under basic operation. For details concerning to Hi-sensible
applications, please contact your dealer.
To activate this setting under cooling operation: change field setting [2-8] to the appropriate
value, matching the requirements of the pre-designed system containing a high sensible
solution.
Value
[2-8]
Te target
2
43°F (6°C)
3
45°F (7°C)
4
46°F (8°C)
5
48°F (9°C)
6
50°F (10°C)
7
52°F (11°C)
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...