Special Control
SiUS342303E
119
Part 4 Functions and Control
Note(s)
7.4 Outdoor
Unit
Rotation
In the case of multi outdoor unit system, this outdoor unit rotation prevents the compressor from
breaking down due to unbalanced oil level between outdoor units.
Details of outdoor unit rotation
In the case of multi outdoor unit system, each outdoor unit is given an operating priority for the
control.
The operating priority of outdoor units is changed by outdoor unit rotation. The outdoor unit rotation
prevents unbalanced oil level between outdoor units by eliminating the long stop of compressors
during partial load.
Timing of outdoor unit rotation
At the beginning of the startup control, or;
After oil return operation, or;
After defrost operation, or;
One of the outdoor units is stopped for 20 minutes or more.
Example) The following diagram shows outdoor unit rotation.
Master unit and sub unit in this section are the names for installation.
They are determined in installation work, and not changed thereafter. (These names are different
from master unit and sub unit for control.)
The outdoor unit connected the control wires (F1 and F2) for the indoor unit should be designated
as master unit.
Consequently, the LED display on the outdoor unit main PCB for master unit, sub unit does not
change.
Normal control
Normal control
Normal control
Normal control
Master
A
A
Startup control
Outdoor unit
rotation
Outdoor unit
rotation
Outdoor unit
rotation
Priority
1
Priority
1
Priority
2
Priority
2
Priority
1
Priority
2
Priority
2
Priority
1
Oil return operation
or defrost operation
Any of outdoor
unit stops for a
period of 20
minutes or more.
Sub
Master
Sub
Master
Sub
Master
Sub
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...