Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
188
2.4 Monitoring Function and Field Settings
The operation of the outdoor unit can further be defined by changing some field settings. Next to
making field settings it is also possible to confirm the current operation parameters of the unit.
Below relevant Monitoring mode (mode 1) and Field setting mode (mode 2) settings are explained
in detail.
Making settings is done via the master outdoor unit.
2.4.1 Mode 1
Mode 1 can be used to monitor the current situation of the outdoor unit. Some field setting contents
can be monitored as well.
Below the settings in mode 1 are explained.
[1-0]:
shows whether the unit you are checking is a master or sub unit.
No indication: undefined situation
0: outdoor unit is master unit
1: outdoor unit is sub unit
Master and sub indications are relevant in multiple outdoor unit system configurations.
The allocation of which outdoor unit is master and sub is decided by the unit’s logic.
The master unit must be used to input field settings in mode 2.
[1-1]:
shows the status of night-time low noise operation.
0: unit is currently not operating under low noise restrictions
1: unit is currently operating under low noise restrictions
Night-time low noise operation reduces the sound generated by the unit compared to
nominal operating conditions.
Night-time low noise operation can be set in mode 2. There are two methods to activate
night-time low noise operation of the outdoor unit system.
The first method is to enable an automatic night-time low noise operation by field
setting. The unit will operate at the selected low noise level during the selected time
frames.
The second method is to enable night-time low noise operation based on an external
input. For this operation an optional accessory is required.
[1-2]:
shows the status of power consumption limitation operation.
0: unit is currently not operating under power consumption limitations
1: unit is currently operating under power consumption limitation
Power consumption limitation reduces the power consumption of the unit compared to
nominal operating conditions.
Power consumption limitation can be set in mode 2.
There are two methods to activate power consumption limitation of the outdoor unit
system.
The first method is to enable a forced power consumption limitation by field setting. The
unit will always operate at the selected power consumption limitation.
The second method is to enable power consumption limitation based on an external
input. For this operation an optional accessory is required.
[1-5]:
shows the current Te target parameter position.
[1-6]:
shows the current Tc target parameter position.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...