Field Setting from Outdoor Unit
SiUS342303E
205
Part 5 Field Settings and Test Operation
[2-90]:
Indoor unit without power
U4
error generation.
In case an indoor unit needs maintenance or repair on the electric side, it is possible to
keep the rest of the
VRV
DX indoor units operating without power supply to some indoor
unit(s).
Default value: 0 (not active)
Field setting 1: It is possible to operate system without
U4
error when some indoor units
are temporarily without power supply.
Field setting 2: It is possible to operate system with
U4
warning when some indoor units
are temporarily without power supply.
Following conditions need to fulfil:
Maximum equivalent piping length of the farthest indoor less than 120 m (394 ft).
Total index of indoor units without power supply is less than 30% of the nominal
outdoor.
Total capacity of indoor units without power supply is less than 30% of the nominal
one of the outdoor unit.
Operation time is limited to 24 hours period.
It is recommended to shut down connected indoor units at the same floor.
Not possible to use service mode operation (e.g. recovery mode) or BP unit/Hydro
unit connection.
Backup operation has priority over this special feature.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...