SiUS342303E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
172
1.4.23 Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material kit of
air discharge outlet has been installed.) The second code No. is factory set to
01
.
: Factory setting
1.4.24 Swing Pattern Settings (For units with the infrared floor sensor only)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side
by side are set to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
: Factory setting
1.4.25 Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
: Factory setting
FXZQ-TB, FXEQ-P
: Factory setting
Mode
No.
First Code
No.
Second
Code No.
Contents
Ceiling height
13 (23)
0
01
Standard
Lower than 2.7 m (8-3/4 ft)
02
High Ceiling 1
Lower than 3.0 m (10 ft)
03
Higher Ceiling 2
Lower than 3.5 m (11-1/2 ft)
FXHQ-M, FXAQ-P
: Factory setting
Mode
No.
First Code
No.
Second
Code No.
Ceiling height
13 (23)
0
01
Standard
02
Slight increase
03
Normal increase
Mode
No.
First Code
No.
Second
Code No.
Ceiling height
13 (23)
1
01
F: 4-direction airflow
02
T: 3-direction airflow
03
W: 2-direction airflow
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23)
2
01
All direction synchronized swing
02
—
03
Facing swing
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23)
4
01
Upward (Draft prevention)
02
Standard
03
Downward (Ceiling soiling prevention)
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...