Figure. 5.4.27 - 139. Operating characteristics of pole slip protection.
Measured input
The function block uses analog current and voltage measurement values. These values are used for
calculating impedance.
Table. 5.4.27 - 221. Measurement inputs of the pole slip protection function.
Signal
Description
Time base
IL1RMS
RMS measurement of phase L1 (A) current
5ms
IL2RMS
RMS measurement of phase L2 (B) current
5ms
IL3RMS
RMS measurement of phase L3 (C) current
5ms
U
L12
RMS
RMS measurement of voltage U
L1
/V
5ms
U
L23
RMS
RMS measurement of voltage U
L2
/V
5ms
U
L31
RMS
RMS measurement of voltage U
L3
/V
5ms
U
L1
RMS
RMS measurement of voltage U
L12
/V
5ms
U
L2
RMS
RMS measurement of voltage U
L23
/V
5ms
U
L3
RMS
RMS measurement of voltage U
L31
/V
5ms
Pos. Seq. Impedance
Positive sequence impedance
5 ms
General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.4.27 - 222. General settings of the function.
Name
Range
Step Default
Description
Pole slip [78] LN
mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
0: On
Set mode of OOS block.
This parameter is visible only when
Allow setting of individual LN mode is
enabled in
General menu.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
269