9.2.1.16 Power protection (P, Q, S>/<; 32)
Table. 9.2.1.16 - 413. Technical data for the power protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Voltage inputs
U
L1
, U
L2
, U
L3
U
L12
, U
L23
, U
L31
(+ U
0
)
Calculated measurements
Three-phase active, reactive or apparent power (P, Q or S) value based on the chosen or
set nominal amplitude.
Pick-up
Comparator selection
> or <
> or <
-500.000...500.000 %/MVA
N
, setting step 0.005 %/MVA
N
Inaccuracy:
- Active, reactive, or apparent
power
Typically <1.0 %P
SET
Operation time
Definite time function operating
time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (P
M
/P
SET
ratio
1.05
→
)
±1.0 % or ±35 ms
Instant operation time
Start time and instant operation
time (trip):
- PQS
M
/PQS
SET
ratio 1.05
→
<40 ms
Reset
Reset ratio
97 or 103 %P
SET
Instant reset time and start-up
reset
<40 ms
No
Notte!
e!
• The voltage measurement starts from 0.5 V and the current measurement from 25 mA. In
case either or both are missing, the measured magnitude is forced to 0 MW/MVar/MVA.
Please avoid using settings that should operate below the relay's current squelch limit (25 mA
on the relay terminal).
• With very small under power pick-up settings time delay inaccuracy might double.
9.2.1.17 Motor start/ locked rotor monitoring (Ist>; 48/14)
Table. 9.2.1.17 - 414. Technical data for the motor start/locked rotor monitoring function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
RMS phase currents
Pick-up
Pick-up current setting
0.10…40.00 × I
N
, setting step 0.10 × I
N
Inaccuracy:
- Current
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
492
© Arcteq Relays Ltd
IM00021
Содержание AQ-M257
Страница 1: ...AQ M257 Motor protection IED Instruction manual...
Страница 2: ......
Страница 449: ...Figure 7 3 221 Example block scheme A AQ Q M257 M257 Instruction manual Version 2 07 Arcteq Relays Ltd IM00021 447...
Страница 470: ...Figure 8 14 243 Device installation A AQ Q M257 M257 Instruction manual Version 2 07 468 Arcteq Relays Ltd IM00021...