6.1.6 GOOSE
Arcteq relays support both GOOSE publisher and GOOSE subscriber. GOOSE subscriber is enabled
with the "GOOSE subscriber enable" parameter at
Communication
→
Protocols
→
IEC 61850/
GOOSE. The GOOSE inputs are configured using either the local HMI or the AQtivate software.
There are up to 64 GOOSE inputs available for use. Each of the GOOSE inputs also has a
corresponding input quality signal which can also be used in internal logic. The quality is good, when
the input quality is low (that is, when the quality is marked as "0"). The value of the input quality can
increase as a result of a GOOSE time-out or a configuration error, for example. The status and quality
of the various logical input signals can be viewed at the
GOOSE IN status and GOOSE IN quality tabs
at
Control
→
Device I/O
→
Logical signals.
General GOOSE setting
The table below presents general settings for GOOSE publisher.
Table. 6.1.6 - 350. General GOOSE publisher settings.
Name
Range
Description
GOOSE control block 1
simulation bit
0: Disabled
(Default)
1: Enabled
The publisher will publish frames with simulation bit active if enabled. For
GOOSE simulation testing purposes.
GOOSE control block 2
simulation bit
The table below presents general settings for GOOSE subscriber
Table. 6.1.6 - 351. General GOOSE subscriber settings.
Name
Range
Description
GOOSE subscriber enable
0: Disabled
(Default)
1: Enabled
Enables or disables GOOSE subscribing for the device.
Not used GOOSE input
Quality
1: Bad
quality (1)
2: Good
quality (0)
Defines what state should GOOSE input quality signal to be in the logic if the
input has been set as "disabled".
Subscriber checks
GoCBRef
0: No
(Default)
1: Yes
When subscriber sees GOOSE frame it checks APPID and Conf. Rev but can
also check if GoCBRef or SqNum match.
Subscriber checks SqNum
Subscriber process
simulation messages
0: No
(Default)
1: Yes
Subscriber can be set to process frames which are published with simulation bit
high if enabled
GOOSE input settings
The table below presents the different settings available for all 64 GOOSE inputs.
Table. 6.1.6 - 352. GOOSE input settings.
Name
Range
Description
In use
0: No
(Default)
1: Yes
Enables and disables the GOOSE input in question.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
428
© Arcteq Relays Ltd
IM00021
Содержание AQ-M257
Страница 1: ...AQ M257 Motor protection IED Instruction manual...
Страница 2: ......
Страница 449: ...Figure 7 3 221 Example block scheme A AQ Q M257 M257 Instruction manual Version 2 07 Arcteq Relays Ltd IM00021 447...
Страница 470: ...Figure 8 14 243 Device installation A AQ Q M257 M257 Instruction manual Version 2 07 468 Arcteq Relays Ltd IM00021...