Default variations
Table. 6.1.8 - 356. Default variations.
Name
Range
Default
Description
Group 1 variation (BI)
0: Var 1
1: Var 2
0: Var 1
Selects the variation of the binary signal.
Group 2 variation (BI change)
0: Var 1
1: Var 2
1: Var 2
Selects the variation of the binary signal change.
Group 3 variation (DBI)
0: Var 1
1: Var 2
0: Var 1
Selects the variation of the double point signal.
Group 4 variation (DBI change)
0: Var 1
1: Var 2
1: Var 2
Selects the variation of the double point signal.
Group 20 variation (CNTR)
0: Var 1
1: Var 2
2: Var 5
3: Var 6
0: Var 1
Selects the variation of the control signal.
Group 22 variation (CNTR change)
0: Var 1
1: Var 2
2: Var 5
3: Var 6
2: Var 5
Selects the variation of the control signal change.
Group 30 variation (AI)
0: Var 1
1: Var 2
2: Var 3
3: Var 4
4: Var 5
4: Var 5
Selects the variation of the analog signal.
Group 32 variation (AI change)
0: Var 1
1: Var 2
2: Var 3
3: Var 4
4: Var 5
5: Var 7
4: Var 5
Selects the variation of the analog signal change.
Setting the analog change deadbands
Table. 6.1.8 - 357. Analog change deadband settings.
Name
Range
Step
Default
Description
General deadband
0.1…10.0%
0.1%
2%
Determines the general data reporting deadband settings.
Active energy deadband
0.1…1000.0kWh 0.1kWh 2kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0kW
0.1kW
2kW
Determines the data reporting deadband settings for this
measurement.
Reactive
power deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0kVA
0.1kVA
2kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00Hz
0.01Hz
0.1Hz
Determines the data reporting deadband settings for this
measurement.
Current deadband
0.01…50.00A
0.01A
5A
Determines the data reporting deadband settings for this
measurement.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
431
Содержание AQ-M257
Страница 1: ...AQ M257 Motor protection IED Instruction manual...
Страница 2: ......
Страница 449: ...Figure 7 3 221 Example block scheme A AQ Q M257 M257 Instruction manual Version 2 07 Arcteq Relays Ltd IM00021 447...
Страница 470: ...Figure 8 14 243 Device installation A AQ Q M257 M257 Instruction manual Version 2 07 468 Arcteq Relays Ltd IM00021...