Time settings
Starting time setting
0.00…1800.00 s, setting step 0.005 s
Operating mode
Definite time or cumulative I2t sum inverse operating time
With or without a speed switch input
Monitors only starts or both starts and stall
Start time
Max. 5 ms from the detected start-up or locked rotor situation
Inaccuracy:
- Starting
- Definite time operating time
±3% of the set pick-up value > 0.5 × I
N
setting. 5 mA < 0.5 × I
N
setting
±0.5 % or ±10 ms
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Cumulative I2t sum inverse operation time
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio 0.95)
±1.0 % or ±40 ms
Instant operation time
Start time and instant operation time (trip):
- I
M
/I
SET
ratio 1.05
→
<55 ms
Reset
Reset ratio
97 % of the pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.010 …150.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<55 ms
9.2.1.18 Frequent start protection (N>; 66)
Table. 9.2.1.18 - 415. Technical data for the frequent start protection function.
Inputs
Input magnitudes
Motor start monitor set start signals
Dependent on the motor
thermal status
Yes
Settings
Starts when cold
1…100 starts, step 1 start
Starts when hot
1…100 starts, step 1 start
Output data
Monitor data
- Used starts
- Available starts
- Alarms, inhibits, blocks
- Inhibit, alarm time on
- Time since last start
Operation
Start time
Max. 5 ms from the detected start-up
Inaccuracy
Starting
±3% of the set pick-up value > 0.5 × I
N
setting. 5 mA < 0.5 × I
N
setting (from the motor start/
locked rotor monitoring function)
Definite time operating time
±0.5 % or ±10 ms of the counter deduct
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
493