The function's outputs are ALARM START, ALARM, START, TRIP and BLOCKED signals which can be
used for direct I/O controlling and user logic programming. The function generates general time-
stamped ON/OFF events to the common event buffer from each of the five (5) output signals. In the
instant operating mode the function outputs START and TRIP events simultaneously with an equivalent
time stamp. The time stamp resolution is 1 ms. The function also provides a resettable cumulative
counter for the ALARM START, ALARM, START, TRIP and BLOCKED events.
The following figure presents a simplified function block diagram of the power factor protection
function.
Figure. 5.4.22 - 109. Simplified function block diagram of the PF> function.
Measured input
The function block uses power factor values. A -20 ms averaged value of the selected magnitude is
used for pre-fault data registering.
Table. 5.4.22 - 184. Measurement inputs of the PF< function.
Signal
Description
Time base
3PH cos φ
Three-phase cos phi (power factor)
5ms
General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.4.22 - 185. General settings of the function.
Name
Range
Step Default
Description
PF< LN mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
0: On
Set mode of UPF block.
This parameter is visible only when
Allow setting of individual LN
mode is enabled in General menu.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
219