Name
Range
Default
Description
Access level for
Mimic control
0: User
1: Operator
2:
Configurator
3: Super
user
2:
Configurator
Determines which access level is required to be able to control the
programmable control switch via the Mimic.
Events
The programmable control switch function (abbreviated "PCS" in event block names) generates events
from status changes. The user can select which event messages are stored in the main event buffer:
ON, OFF, or both. The function offers five (5) independent switches.
Table. 5.5.6 - 275. Event messages.
Event block name
Event names
PCS
Switch 1 ON
PCS
Switch 1 OFF
PCS
Switch 2 ON
PCS
Switch 2 OFF
PCS
Switch 3 ON
PCS
Switch 3 OFF
PCS
Switch 4 ON
PCS
Switch 4 OFF
PCS
Switch 5 ON
PCS
Switch 5 OFF
5.5.7 Analog input scaling curves
Sometimes when measuring with RTD inputs, milliampere inputs and digital inputs the measurement
might be inaccurate because the signal coming from the source is inaccurate. One common example
of this is tap changer location indication signal not changing linearly from step to step. If the output
difference between the steps are not equal to each other, measuring the incoming signal accurately is
not enough. "Analog input scaling curves" menu can be used to take these inaccuracies into account.
Analog input scaling curve settings can be found at
Measurement
→
AI(mA, DI volt) scaling menu.
Currently following measurements can be scaled with analog input scaling curves:
• RTD inputs and mA inputs in "RTD & mA input" option cards
• mA inputs in "mA output & mA input" option cards
• Digital input voltages
Table. 5.5.7 - 276. Main settings (input channel).
Name
Range
Step
Default
Description
Analog input
scaling
0: Disabled
1: Activated
-
0:
Disabled Enables and disables the input.
Scaling curve 1...4
0: Disabled
1: Activated
-
0:
Disabled
Enables and disables the scaling curve and the input
measurement.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
361
Содержание AQ-M257
Страница 1: ...AQ M257 Motor protection IED Instruction manual...
Страница 2: ......
Страница 449: ...Figure 7 3 221 Example block scheme A AQ Q M257 M257 Instruction manual Version 2 07 Arcteq Relays Ltd IM00021 447...
Страница 470: ...Figure 8 14 243 Device installation A AQ Q M257 M257 Instruction manual Version 2 07 468 Arcteq Relays Ltd IM00021...