The outputs for the function are the following:
• motor stopped
• motor starting
• motor running
• motor stalled
• missing phase
• load normal
• overloading
• high overcurrent signals.
The signals can be used in indication or in application logics. They are also the basis of the events the
function generates (if so chosen).
The following figure presents a simplified function block diagram of the motor status monitoring
function.
Figure. 5.4.17 - 92. Simplified function block diagram of the motor status monitoring function.
The function's outputs are dependent on the motor data the user has set. The following two
diagram present the function's outputs in various situations.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
180
© Arcteq Relays Ltd
IM00021