Name
Range
Step
Default
Protection
functions
Description
Max locked
rotor current A 0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The maximum locked rotor current in amperes.
Max overload
current
0.1…40.0xI
n
0.1xI
n
2.0xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's maximum overload current. Exceeding
this setting stalls the motor. This setting defines when
the thermal replica switches to the short (stall) time
constant. As long as the current stays below this
setting value, the motor should run even when
overloaded.
Max overload
current A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's maximum overload current in amperes.
No load
current <
0.1…40.0xI
n
0.1xI
n
0.2xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Undercurrent
(I<; 37)
The motor's no load current. This setting defines the
“Stopped” condition when the current is below this
setting value. Also, when the current is below this
value, the undercurrent protection stage is locked.
No load
current < A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Undercurrent
(I<; 37)
The motor's no load current in amperes.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
186
© Arcteq Relays Ltd
IM00021