Name
Range
Step Default
Description
Control Authority switch
0: Remote
Control
1: Station
Level Control
-
0:
Remote
Control
The device can be set to allow object control via IEC 61850
only from clients that are of category Station level control. This
would mean that other Remote control clients would not be
allowed to control. In Remote control mode all IEC 61850
clients of both remote and station level category are allowed
to control objects.
Ethernet port
0: All
1: COM A
2: Double
ethernet card
-
0: All
Determines which ports use IEC61850.
Configure GOOSE
Subscriber from CID file
allowed
0: Disabled
1: Allowed
-
0:
Disabled
In edition 2 of IEC 61850 GOOSE subscriber configuration is
a part of the CID file. Determines if it is possible to import
published GOOSE settings of another device with a CID file
and set them to GOOSE input at
Tools
→
Communication
→
IEC 61850
→
GOOSE subscriptions.
General deadband
0.1…10.0 %
0.1
%
2 %
Determines the general data reporting deadband settings.
Active energy deadband 0.1…1000.0
kWh
0.1
kWh
2 kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0
kW
0.1
kW
2 kW
Determines the data reporting deadband settings for this
measurement.
Reactive
power deadband
0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0
kVA
0.1
kVA
2 kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00 Hz
0.01
Hz
0.1 Hz
Determines the data reporting deadband settings for this
measurement.
Current deadband
0.01…50.00 A
0.01
A
5 A
Determines the data reporting deadband settings for this
measurement.
Residual
current deadband
0.01…50.00 A
0.01
A
0.2 A
Determines the data reporting deadband settings for this
measurement.
Voltage deadband
0.01…5000.00
V
0.01
V
200 V
Determines the data reporting deadband settings for this
measurement.
Residual
voltage deadband
0.01…5000.00
V
0.01
V
200 V
Determines the data reporting deadband settings for this
measurement.
Angle
measurement deadband 0.1…5.0 deg
0.1
deg
1 deg
Determines the data reporting deadband settings for this
measurement.
Integration time
0…10 000 ms
1 ms
0 ms
Determines the integration time of the protocol. If this
parameter is set to "0 ms", no integration time is in use.
GOOSE Ethernet port
0: All
1: COM A
2: Double
ethernet card
-
0: All
Determines which ports can use GOOSE communication.
For more information on the IEC 61850 communication protocol support, please refer to the
conformance statement documents (
→
AQ-200 series
→
Resources).
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
427