The variables the user can set are binary signals from the system. The blocking signal needs to reach
the device minimum of 5 ms before the set operating delay has passed in order for the blocking to
activate in time.
Events and registers
The inadvertent energizing protection function (abbreviated "IAE" in event block names) generates
events and registers from the status changes in START, TRIP and BLOCKED. The user can select
which event messages are stored in the main event buffer: ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.4.25 - 213. Event messages.
Event block name
Event names
IAE1
Start ON
IAE1
Start OFF
IAE1
Trip ON
IAE1
Trip OFF
IAE1
Block ON
IAE1
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for START, TRIP or BLOCKED. The table below
presents the structure of the function's register content.
Table. 5.4.25 - 214. Register content.
Date and time
Event
Phase current
Phase voltage
Used SG
dd.mm.yyyyhh:mm:ss.mss Event
name
Phase 1,2,3 [A,B,C]
currents
Phase AB, BC and CA
voltages
Setting group 1...8
active
5.4.26 Inadvertend energizing protection (I> U< I.A.E; 50/27)
Inadvertent energizing protection function is intended to be used for protection the generator from
connecting the generator to network when it is not rotating. A machine that is accidentally energized
from the power system can be damaged or completely destroyed.
The power protection function uses a total of eight (8) separate setting groups which can be selected
from one common source.
The function can operate on instant or time-delayed mode.
The operational logic consists of the following:
• input magnitude processing
• threshold comparator
• block signal check
• time delay characteristics
• output processing.
The inputs for the function are the following:
• operating mode selections
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
264
© Arcteq Relays Ltd
IM00021
Содержание AQ-M257
Страница 1: ...AQ M257 Motor protection IED Instruction manual...
Страница 2: ......
Страница 449: ...Figure 7 3 221 Example block scheme A AQ Q M257 M257 Instruction manual Version 2 07 Arcteq Relays Ltd IM00021 447...
Страница 470: ...Figure 8 14 243 Device installation A AQ Q M257 M257 Instruction manual Version 2 07 468 Arcteq Relays Ltd IM00021...