background image

Relion

®

 615 series

Line Differential Protection and Control

RED615

Product Guide

Содержание RED615 ANSI

Страница 1: ...Relion 615 series Line Differential Protection and Control RED615 Product Guide...

Страница 2: ...1 23 Selection and ordering data 52 24 Accessories and ordering data 55 25 Tools 55 26 Terminal diagrams 58 27 Certificates 60 28 References 60 29 Functions codes and symbols 61 30 Document revision h...

Страница 3: ...protection of overhead line and cable feeders in isolated neutral resistance earthed compensated impedance earthed and solidly earthed networks Once the IED has been given the application specific set...

Страница 4: ...h fault protection instance 2 o2 3 4 Admittance based earth fault protection instance 3 o2 3 4 Wattmetric based earth fault protection instance 1 o2 3 4 Wattmetric based earth fault protection instanc...

Страница 5: ...urement instance 1 Residual voltage measurement included o optional at the time of order 1 The instances of a protection function represent the number of identical function blocks available in a stand...

Страница 6: ...protection The line differential protection function includes a stabilized low stage and an instantaneous high stage The stabilized low stage provides sensitive differential protection and remains st...

Страница 7: ...GUID 81A76312 4CC1 4AE8 A0A3 14C9800EE0E2 V3 EN Figure 2 Protection function overview of standard configuration B Line Differential Protection and Control 1MRS756500 F RED615 Product version 4 0 ABB 7...

Страница 8: ...location of the current transformers in the local and the remote substation Combining horizontal GOOSE communication over a station bus and binary signal transfer over the protection communication lin...

Страница 9: ...elective short circuit protection With RED615 line differential protection IEDs the faulty part of the network can be selectively isolated thus securing power distribution to the healthy part of the n...

Страница 10: ...2 4EDC 8C2D 9C968FA05C66 V3 EN Figure 5 RED615 protecting an interconnecting feeder between two primary distribution substations Line Differential Protection and Control 1MRS756500 F RED615 Product ve...

Страница 11: ...83C4 E1A7FCE811B0 V3 EN Figure 6 Line differential protection of an overhead line feeder using RED615 with the standard configuration B Line Differential Protection and Control 1MRS756500 F RED615 Pro...

Страница 12: ...sent to the remote end directional E F protection stage preventing tripping of the circuit breaker If the earth fault is within the protected zone no blocking signal will be issued and the internal fa...

Страница 13: ...81A1 V3 EN Figure 7 Line differential protection of an overhead line feeder using RED615 with the standard configuration C and auto reclosing option Line Differential Protection and Control 1MRS756500...

Страница 14: ...s are among the distinctive features of the protection system approach enabled by the full implementation of the IEC 61850 substation automation standard At the substation level COM600 uses the data c...

Страница 15: ...IEDs Grid Automation controller COM600 and System 800xA 6 Control RED615 integrates functionality for the control of a circuit breaker via the front panel HMI or by means of remote controls In additi...

Страница 16: ...gration enables releasing of some initially reserved binary inputs and outputs of the IED in the standard configuration The suitability of the binary outputs of the IED which have been selected for co...

Страница 17: ...urrent values time stamp etc The fault recording can be triggered by the start signal or the trip signal of a protection block or by both The available measurement modes include DFT RMS and peak to pe...

Страница 18: ...5 kV RMS level of isolation between the pilot wire terminals and ground The RPW600 modems master and follower are galvanically connected to either end of the pilot wire and optically connected to the...

Страница 19: ...nputs and outputs Depending on the standard configuration selected the IED is equipped with three phase current inputs and one residual current input for non directional earth fault protection and cur...

Страница 20: ...stations as defined by the IEC 61850 standard Further the IED supports the sending and receiving of analog values using GOOSE messaging Analog GOOSE messaging enables fast transfer of analog measureme...

Страница 21: ...both serial and TCP modes for connection to one master Further changing of the active setting group is supported When the IED uses the RS 485 bus for the serial communication both two and four wire co...

Страница 22: ...76E519C V3 EN Figure 12 Self healing Ethernet ring solution Table 6 Supported station communication interfaces and protocols Interfaces Protocols Ethernet Serial 100BASE TX RJ 45 RS 232 RS 485 Fibre o...

Страница 23: ...n time in the auxiliary DC voltage without resetting the IED 50 ms at Unrated Uauxvariation 38 110 of Un 38 264 V AC 50 120 of Un 12 72 V DC 80 120 of Un 38 4 300 V DC Start up threshold 19 2 V DC 24...

Страница 24: ...d or phase current Table 10 Binary inputs Description Value Operating range 20 of the rated voltage Rated voltage 24 250 V DC Current drain 1 6 1 9 mA Power consumption 31 0 570 0 mW Threshold voltage...

Страница 25: ...series 5 A 3 A 1 A Minimum contact load 100 mA at 24 V AC DC Trip circuit supervision TCS Control voltage range 20 250 V AC DC Current drain through the supervision circuit 1 5 mA Minimum voltage ove...

Страница 26: ...Power consumption 10 20 mW 1 According to 200 04 IRIG standard Table 18 Degree of protection of flush mounted IED Description Value Front side IP 54 Rear side connection terminals IP 20 Table 19 Envi...

Страница 27: ...eat test 6 cycles 12 h 12 h at 25 C 55 C humidity 93 IEC 60068 2 30 Change of temperature test 5 cycles 3 h 3 h at 25 C 55 C IEC60068 2 14 Storage test 96 h at 40 C 96 h at 85 C IEC 60068 2 1 IEC 6006...

Страница 28: ...III 10 V m rms f 80 2700 MHz IEC 61000 4 3 IEC 60255 22 3 class III 10 V m f 900 MHz ENV 50204 IEC 60255 22 3 class III 20 V m rms f 80 1000 MHz IEEE C37 90 2 2004 Fast transient disturbance test IEC...

Страница 29: ...distance 230 1000 MHz 47 dB V m quasi peak measured at 10 m distance Table 22 Insulation tests Description Type test value Reference Dielectric tests 2 kV 50 Hz 1 min 500 V 50 Hz 1 min communication I...

Страница 30: ...5 EN 60255 1 2009 Table 25 EMC compliance Description Reference EMC directive 2004 108 EC Standard EN 50263 2000 EN 60255 26 2007 Table 26 RoHS compliance Description Complies with RoHS directive 2002...

Страница 31: ...al current 2 x High operate value and fn 50 Hz with galvanic pilot wire link 5 ms 4 Low operate value multiples in range of 1 5 to 20 Table 28 Line differential protection LNPLDF main settings Paramet...

Страница 32: ...alue 22 ms 24 ms 25 ms Reset time 40 ms Reset ratio Typical 0 96 Retardation time 30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time...

Страница 33: ...05 15 00 0 01 Operate delay time PHLPTOC 40 200000 ms 10 PHHPTOC 40 200000 ms 10 PHIPTOC 20 200000 ms 10 Operating curve type1 PHLPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13...

Страница 34: ...ime 40 ms Reset ratio Typical 0 96 Retardation time 30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical va...

Страница 35: ...5 00 0 01 Operate delay time EFLPTOC 40 200000 ms 10 EFHPTOC 40 200000 ms 10 EFIPTOC 20 200000 ms 10 Operating curve type1 EFLPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14...

Страница 36: ...me 40 ms Reset ratio Typical 0 96 Retardation time 30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical val...

Страница 37: ...13 14 15 17 18 19 DEFHPDEF Definite or inverse time Curve type 1 3 5 15 17 Operation mode DEFLPDEF and DEFHPDEF 1 Phase angle 2 IoSin 3 IoCos 4 Phase angle 80 5 Phase angle 88 1 For further reference...

Страница 38: ...in IEF mode INTRPTEF 2 20 Min operate current INTRPTEF 0 01 1 00 x In 0 01 Table 38 Admittance based earth fault protection EFPADM Characteristic Value Operation accuracy1 At the frequency f fn 1 0 o...

Страница 39: ...0 Admittance circle midpoint conductance Circle susceptance 500 00 500 00 mS 0 01 0 00 Admittance circle midpoint susceptance Conductance forward 500 00 500 00 mS 0 01 1 00 Conductance threshold in fo...

Страница 40: ...ue before fault 0 0 p u fn 50 Hz results based on statistical distribution of 1000 measurement 2 Includes the delay of the signal output contact Table 41 Wattmetric based earth fault protection WPWDE...

Страница 41: ...current before fault 0 0 x In harmonics fault current 2 0 x Start value Results based on statistical distribution of 1000 measurement 2 Includes the delay of the signal output contact 3 Maximum Start...

Страница 42: ...ROVPTOV 0 010 1 000 x Un 0 001 Operate delay time ROVPTOV 40 300000 ms 1 Table 46 Negative phase sequence overcurrent protection NSPTOC Characteristic Value Operation accuracy Depending on the freque...

Страница 43: ...rt time 70 ms Reset time 40 ms Reset ratio Typical 0 96 Retardation time 35 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n x fn...

Страница 44: ...check Retrip time CCBRBRF 0 60000 ms 10 CB failure delay CCBRBRF 0 60000 ms 10 CB fault delay CCBRBRF 0 60000 ms 10 Table 52 Three phase thermal overload protection for feeders T1PTTR Characteristic...

Страница 45: ...ture level for operate T1PTTR 20 0 200 0 C 0 1 Alarm value Temperature level for start alarm T1PTTR 20 0 150 0 C 0 1 Reclose temperature Temperature for reset of block reclose after operate T1PTTR 20...

Страница 46: ...t inv 2 ANSI Very inv 3 ANSI Norm inv 4 ANSI Mod inv 5 ANSI Def Time 6 L T E inv 7 L T V inv 8 L T inv 9 IEC Norm inv 10 IEC Very inv 11 IEC inv 12 IEC Ext inv 13 IEC S T inv 14 IEC L T inv 15 IEC Def...

Страница 47: ...ntact Table 58 Current circuit supervision CCRDIF main settings Parameter Values Range Unit Description Start value 0 05 0 20 x In Minimum operate current differential level Maximum operate current 1...

Страница 48: ...rol functions Table 59 Autoreclosing DARREC Characteristic Value Operate time accuracy 1 0 of the set value or 20 ms Line Differential Protection and Control 1MRS756500 F RED615 Product version 4 0 48...

Страница 49: ...01 4 00 x In Suppression of harmonics DFT 50 dB at f n x fn where n 2 3 4 5 Table 62 Residual current measurement RESCMMXU Characteristic Value Operation accuracy Depending on the frequency of the cu...

Страница 50: ...d using the web browser based user interface The default SLD can be modified according to user requirements by using the graphical display editor in PCM600 The local HMI includes a push button L R for...

Страница 51: ...g purposes the IED cases can be equipped with test switches type RTXP 18 which can be mounted side by side with the IED cases Mounting methods Flush mounting Semi flush mounting Semi flush mounting in...

Страница 52: ...A N 1 X E GUID 4753ED2D 5A23 4F34 A689 9E47511ED8C7 V5 EN Description 4 8 Standard configurations analog and binary I O options Standard configuration descriptions in short A Line differential protect...

Страница 53: ...ential single mode fibre LC BK Line differential multi mode fibre LC NA Line differential single mode fibre LC NB Ethernet 100Base TX RJ 45 Line differential multi mode fibre LC NG Ethernet 100Base TX...

Страница 54: ...and directional earth fault protection only for std configuration B C Harmonics based earth fault protection and directional earth fault protection only for std configuration B D Harmonics based earth...

Страница 55: ...included in the delivery 2RCA021952A0003 19 rack mounting kit for one IED and one RTXP24 test switch the test switch is not included in the delivery 2RCA022561A0003 Replacement kit for a Str mberg SP_...

Страница 56: ...limited to read only access by means of PCM600 The IED connectivity package is a collection of software and specific IED information which enable system products and tools to connect and interact wit...

Страница 57: ...nagement DNP3 communication configuration communication management IEC 60870 5 103 communication configuration communication management Saving of IED parameter settings in the tool Disturbance record...

Страница 58: ...rminal diagrams GUID FBFA9940 E37D 4C32 A083 0367AAEDE267 V2 EN Figure 19 Terminal diagram for configuration A and C Line Differential Protection and Control 1MRS756500 F RED615 Product version 4 0 58...

Страница 59: ...GUID A05D9233 4377 48D7 9F00 4218F0E7D4DC V2 EN Figure 20 Terminal diagram for configuration B Line Differential Protection and Control 1MRS756500 F RED615 Product version 4 0 ABB 59...

Страница 60: ...RED615 protection IED on the product page For information regarding the RPW600 modems please refer to the RPW600 User s Guide document id 6621 2260 The document is available for download on the RED61...

Страница 61: ...HPDEF1 Io 67N 2 Admittance based earth fault protection EFPADM1 Yo 1 21YN 1 EFPADM2 Yo 2 21YN 2 EFPADM3 Yo 3 21YN 3 Wattmetric based earth fault protection WPWDE1 Po 1 32N 1 WPWDE2 Po 2 32N 2 WPWDE3 P...

Страница 62: ...2 I O DC 2 I O DC 2 DCSXSWI3 I O DC 3 I O DC 3 Earthing switch indication ESSXSWI1 I O ES 1 I O ES 1 ESSXSWI2 I O ES 2 I O ES 2 Auto reclosing DARREC1 O I 79 Condition monitoring Circuit breaker condi...

Страница 63: ...ed to correspond to the product version C 2010 06 11 3 0 Content updated to correspond to the product version D 2010 06 29 3 0 Terminology updated E 2010 09 07 3 0 Content updated F 2012 05 11 4 0 Con...

Страница 64: ...64...

Страница 65: ......

Страница 66: ......

Страница 67: ......

Страница 68: ...Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094 www abb com substationautomation 1MRS756500 F Copyright 2012 ABB All rights reserved...

Отзывы: