Table 9. Energizing inputs
Description
Value
Rated frequency
50/60 Hz
Current inputs
Rated current, I
n
1/5 A
1)
Thermal withstand capability:
• Continuously
4 A
20 A
• For 1 s
100 A
500 A
Dynamic current withstand:
• Half-wave value
250 A
1250 A
Input impedance
<100 mΩ
<20 mΩ
Voltage inputs
Rated voltage
60...210 V AC
Voltage withstand:
• Continuous
240 V AC
• For 10 s
360 V AC
Burden at rated voltage
<0.05 VA
1)
Residual current and/or phase current
Table 10. Binary inputs
Description
Value
Operating range
±20% of the rated voltage
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
18...176 V DC
Reaction time
3 ms
Table 11. Signal output X100: SO1
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/
R<40 ms
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC