Table 39. Admittance-based earth-fault protection (EFPADM) main settings
Parameter
Values (Range)
Unit
Step
Default
Description
Voltage start value
0.05...5.00
xUn
0.01
0.05
Voltage start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Operation mode
1=Yo
2=Go
3=Bo
4=Yo, Go
5=Yo, Bo
6=Go, Bo
7=Yo, Go, Bo
1=Yo
Operation criteria
Operate delay time
60...200000
ms
10
60
Operate delay time
Circle radius
0.05...500.00
mS
0.01
1.00
Admittance circle
radius
Circle conductance
-500.00...500.00
mS
0.01
0.00
Admittance circle
midpoint,
conductance
Circle susceptance
-500.00...500.00
mS
0.01
0.00
Admittance circle
midpoint,
susceptance
Conductance forward
-500.00...500.00
mS
0.01
1.00
Conductance
threshold in forward
direction
Conductance reverse
-500.00...500.00
mS
0.01
-1.00
Conductance
threshold in reverse
direction
Conductance tilt Ang
-30...30
deg
1
0
Tilt angle of
conductance
boundary line
Susceptance forward
-500.00...500.00
mS
0.01
1.00
Susceptance
threshold in forward
direction
Susceptance reverse
-500.00...500.00
mS
0.01
-1.00
Susceptance
threshold in reverse
direction
Susceptance tilt Ang
-30...30
deg
1
0
Tilt angle of
susceptance
boundary line
Line Differential Protection and Control
1MRS756500 F
RED615
Product version: 4.0
ABB
39
Содержание RED615 ANSI
Страница 1: ...Relion 615 series Line Differential Protection and Control RED615 Product Guide...
Страница 64: ...64...
Страница 65: ......
Страница 66: ......