Table 47. Negative phase-sequence overcurrent protection (NSPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
NSPTOC
0.01...5.00 x I
n
0.01
Time multiplier
NSPTOC
0.05...15.00
0.01
Operate delay time
NSPTOC
40...200000 ms
10
Operating curve type
1)
NSPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15,
17, 18, 19
1)
For further reference please refer to the Operating characteristics table
Table 48. Phase discontinuity protection (PDNSPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2 Hz
±2% of the set value
Start time
< 70 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5,…
Table 49. Phase discontinuity protection (PDNSPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value (Current ratio
setting I
2
/I
1
)
PDNSPTOC
10...100 %
1
Operate delay time
PDNSPTOC
100...30000 ms
1
Min phase current
PDNSPTOC
0.05...0.30 x I
n
0.01
Table 50. Circuit breaker failure protection (CCBRBRF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 x I
n
Operate time accuracy
±1.0% of the set value or ±20 ms
Line Differential Protection and Control
1MRS756500 F
RED615
Product version: 4.0
ABB
43