Table 21. Electromagnetic compatibility tests, continued
Description
Type test value
Reference
Voltage dips and short interruptions:
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Power frequency immunity test:
• Common mode
• Differential mode
Binary inputs only
300 V rms
150 V rms
IEC 61000-4-16
IEC 60255-22-7, class A
Conducted common mode
disturbances:
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
IEC 61000-4-16
Emission tests:
EN 55011, class A
IEC 60255-25
• Conducted
0.15-0.50 MHz
< 79 dB(µV) quasi peak
< 66 dB(µV) average
0.5-30 MHz
< 73 dB(µV) quasi peak
< 60 dB(µV) average
• Radiated
30-230 MHz
< 40 dB(µV/m) quasi peak, measured at
10 m distance
230-1000 MHz
< 47 dB(µV/m) quasi peak, measured at
10 m distance
Table 22. Insulation tests
Description
Type test value
Reference
Dielectric tests
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
IEC 60255-5 and
IEC 60255-27
Impulse voltage test
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J, communication
IEC 60255-5 and
IEC 60255-27
Insulation resistance measurements >100 MΏ, 500 V DC
IEC 60255-5 and
IEC 60255-27
Protective bonding resistance
<0.1 Ώ, 4 A, 60 s
IEC 60255-27
Table 23. Mechanical tests
Description
Reference
Requirement
Vibration tests (sinusoidal)
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
Class 2
Shock and bump test
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
Class 2
Seismic test
IEC 60255-21-3
Class 2
Line Differential Protection and Control
1MRS756500 F
RED615
Product version: 4.0
ABB
29