Table 37. Transient/intermittent earth-fault protection (INTRPTEF) main settings
Parameter
Function
Value (Range)
Step
Directional mode
INTRPTEF
1=Non-directional
2=Forward
3=Reverse
-
Operate delay time
INTRPTEF
40...1200000 ms
10
Voltage start value (voltage
start value for transient EF)
INTRPTEF
0.01...0.50 x Un
0.01
Operation mode
INTRPTEF
1=Intermittent EF
2=Transient EF
-
Peak counter limit (Min
requirement for peak
counter before start in IEF
mode)
INTRPTEF
2...20
-
Min operate current
INTRPTEF
0.01...1.00 x In
0.01
Table 38. Admittance-based earth-fault protection (EFPADM)
Characteristic
Value
Operation accuracy
1)
At the frequency f = f
n
±1.0% or ±0.01 mS
(In range of 0.5 - 100 mS)
Start time
2)
Minimum
Typical
Maximum
56 ms
60 ms
64 ms
Reset time
40 ms
Operate time accuracy
±1.0% of the set value of ±20 ms
Suppression of harmonics
-50 dB at f = n x f
n
, where n = 2, 3, 4, 5,…
1)
Uo = 1.0 x Un
2)
Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.
Line Differential Protection and Control
1MRS756500 F
RED615
Product version: 4.0
38