Protection functions
Table 27. Line differential protection (LNPLDF)
Characteristics
Value
Operation accuracy
1)
Depending on the frequency of the current measured: f
n
±2 Hz
Low stage
±2.5% of the set value
High stage
±2.5% of the set value
Minimum
Typical
Maximum
High stage, operate time
2)3)
22 ms
25 ms
29 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time (Low stage)
< 40 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the set value or ±20 ms
4)
1)
With the symmetrical communication channel (as when using dedicated fiber optic).
2)
Without additional delay in the communication channel (as when using dedicated fiber optic).
3)
Including the delay of the output contact. When differential current = 2 x
High operate value and f
n
= 50 Hz with galvanic pilot wire link + 5 ms.
4)
Low operate value multiples in range of 1.5 to 20.
Table 28. Line differential protection (LNPLDF) main settings
Parameter
Values (Range)
Unit
Description
High operate value
200...4000
% I
n
Instantaneous stage operate value
Low operate value
10...200
% I
n
Basic setting for the stabilized
stage start
Operate delay time
45...200000
ms
Operate delay time for stabilized
stage
Operate curve type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
Selection of time delay curve for
stabilized stage
Time multiplier
0.05...15.00
Time multiplier in IDMT curves
Start value 2.H
10...50
%
The ratio of the 2. harmonic
component to fundamental
component required for blocking
CT ratio correction
0.200...5.000
Remote phase current transformer
ratio correction
Line Differential Protection and Control
1MRS756500 F
RED615
Product version: 4.0
ABB
31