Figure. 5.4.18 - 100. Outputs in long motor starting, with a speed switch.
The speed switch is also useful when the motor start is naturally very long due to a high accelerating
mass. In such applications a speed switch is required to know whether the start-up is actually
happening, or whether the load is jammed and the motor is standing still with its rotor locked.
If the motor start-up with a speed switch exceeds the allowed safe stall time of the motor specifications,
the function trips.