Name
Range
Step Default
Description
Time
delay for
releasing
start
condition
0.000...1800.000
s
0.005
s
0.250 s
When measured voltage rises over
Voltage limit U< setting the function will
wait for the duration of this parameter setting before disabling start
condition. If each phase current rises over
Current limit I>/< setting while
start release is still going on the function will trip.
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.4.25 - 212. Information displayed by the function.
Name
Range
Step
Description
I>U< I.A.E LN
behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of IAE block.
This parameter is visible only when
Allow setting of individual LN
mode is enabled in General menu.
I>U<
I.A.E condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays status of the protection function.
Expected
operating time
0.000...1800.000s
0.005s Displays the expected operating time when a fault occurs.
Time remaining
to trip
-1800.000...1800.000s 0.005s When the function has detected a fault and counts down time towards a
trip, this displays how much time is left before tripping occurs.
Measured
voltage / set
now
0.00...1250.00
0.01
The ratio between the positive sequence voltage and the pick-up
setting.
Measured min
current / set
now
0.00...1250.00
0.01
The ratio between the lowest measured phase current and the pick-up
setting.
Function blocking
The block signal is checked in the beginning of each program cycle. The blocking signal is received
from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when
the pick-up element activates, a START signal is generated and the function proceeds to the time
characteristics calculation.
If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and
the function does not process the situation further. If the START function has been activated before the
blocking signal, it resets and the release time characteristics are processed similarly to when the pick-
up signal is reset.
The blocking of the function causes an HMI display event and a-time stamped blocking event with
information of the impedance values.
The blocking signal can also be tested in the commissioning phase by a software switch signal when
the relay's testing mode "Enable stage forcing" is activated (
General
→
Device).
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
263