Name
Range
Step
Default
Description
Turnpoint
2
0.01…50.00×I
n
0.01×I
n
3.00×I
n
Turnpoint 2 for the differential characteristics.
Slope 2
0.01…250.00%
0.01%
200.00% Slope 2 of the differential characteristics-
Enable
harmonic
blocking
0: No harmonic
blocking
1: 2
nd
harmonic
blocking
2: 5
th
harmonic
blocking
3: 2
nd
and 5
th
harmonic blocking
-
1: 2
nd
harmonic
blocking
The selection of the internal blockings to be used for the detection of
transformer normal operations that cause differential currents.
2
nd
harmonic
blocking
pick-up
0.01…50.00%
0.01%
15.00%
The pick-up detection for the 2
nd
harmonic blocking stage. This
setting is only visible if the "Enable harmonic blocking" setting is set
to "1" or "3".
5
th
harmonic
blocking
pick-up
0.01…50.00%
0.01%
35.00%
The pick-up detection for the 5
th
harmonic blocking stage. This
setting is only visible if the "Enable harmonic blocking" setting is set
to "2" or "3".
Enable
Idi> stage
0: Disabled
1: Enabled
-
1:
Enabled
The selection of whether the non-biased and the non-blocked
differential stage is enabled or disabled.
Idi> Non-
biased
pick-up
200.00…1500.00% 0.01%
600.00% The pick-up setting for the non-biased and non-blocked differential
stage. This setting is only visible if the "Enable Idi> stage" is disabled.
HV I0d>
Pick-up
0.01…100.00%
0.01%
10.00%
The base sensitivity for the HV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
HV side" setting is enabled.
HV I0d>
Turnpoint
1
0.01…50.00×I
n
0.01×I
n
1.00×I
n
Turnpoint 1 for the HV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
HV side" setting is enabled.
HV I0d>
Slope 1
0.01…250.00%
0.01%
10.00%
Slope 1 of the HV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
HV side" setting is enabled.
HV I0d>
Turnpoint
2
0.01…50.00×I
n
0.01×I
n
3.00×I
n
Turnpoint 2 for the HV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
HV side" setting is enabled.
HV I0d>
Slope 2
0.01…250.00%
0.01%
200.00%
Slope 2 of the HV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
HV side" setting is enabled.
LV I0d>
Pick-up
0.01…100.00%
0.01%
10.00%
The base sensitivity for the LV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
LV side" setting is enabled.
LV I0d>
Turnpoint
1
0.01…50.00×I
n
0.01×I
n
1.00×I
n
Turnpoint 1 for the LV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
LV side" setting is enabled.
LV I0d>
Slope 1
0.01…250.00%
0.01%
10.00%
Slope 1 of the LV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
LV side" setting is enabled.
LV I0d>
Turnpoint2
0.01…50.00×I
n
0.01×I
n
3.00×I
n
Turnpoint 2 for the LV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
LV side" setting is enabled.
LV I0d>
Slope 2
0.01…250.00%
0.01%
200.00%
Slope 2 of the LV side restricted earth fault differential
characteristics. This setting is only visible if the "Enable I0d> (REF)
LV side" setting is enabled.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
318
© Arcteq Relays Ltd
IM00021