Name
Range
Step Default Prot.funcs.
Description
Max
overload
current
A
0.1...5
000.0A
0.1A
-
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The maximum overload current of the motor in amperes.
Hot
condition
theta
limit
0.0…100.0% 0.1%
70%
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
- Machine
thermal
overload
protection
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
Setting the motor's thermal limit in a hot or a cold situation.
When this setting value is not exceed while a locked rotor
situation occurs, the function uses a cold stall curve adjusted
with the actually used thermal capacity. The function uses a hot
stall curve when this setting value is exceeded. This setting also
applies to starts when the hot/cold selection is in use. Please
note that using this setting requires that the Machine thermal
overload protection (Tm>) function is activated and in use.
Safe stall
time cold 0.1…600.0s
0.1s
20.0s
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
- Machine
thermal
overload
protection
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The safe stall time when the motor is cold. Unless this value is
specified, it is set to be equal to the hot stall time. Most
probably this leads to overprotection with the cold motor stall
(best case scenario). This setting value is used for the cold
thermal stall curve selection in automatic control. This
parameter is also used in the motor start-up and the number of
starts calculations.
Safe stall
time hot
0.1…600.0s
0.1s
15.0s
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
- Machine
thermal
overload
protection
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The safe stall time when the motor is hot. This setting value is
used for the hot thermal stall curve selection in automatic
control. This parameter is also used in the motor start-up and
the number of starts calculations.
Table. 5.4.21 - 180. Pick-up settings.
Name
Description
Range
Step
Default
I
set
Pick-up setting
0.10…40.00xI
n
0.10xI
n
6.00xI
n
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
215