The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Using
Block setting to prevent nuisance trips
It is recommended to use the
Block setting parameter to prevent the relay from tripping in a situation
where the network is de-energized. When the measured voltage drops below the set value, the relay
does not give a tripping signal. If the measured voltage has dropped below the
Block setting
parameter, the blocking continues until all of the line voltages have increased above the U< pick-up
setting. Please see the image below for a visualization of this function. If the block level is set to zero
(0), blocking is not in use.
Figure. 5.4.11 - 73. Example of the block setting operation.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.4.11 - 118. Information displayed by the function.
Name
Range
Step
Description
U< LN
behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of UV block.
This parameter is visible only when
Allow setting of individual LN
mode is enabled in General menu.
U< pick-
up setting
0.0...1 000 000.0V
0.1V
The primary voltage required for tripping. The displayed pick-up voltage
level depends on the pick-up setting and the voltage transformer
settings.
U< block
setting
0.0...1 000 000.0V
0.1V
The primary voltage level required for trip blocking. If the measured
voltage is below this value, the network is considered de-energized and
the function will not trip. To deactivate the blocking the measured
voltage must exceed the pick-up setting value.
Expected
operating
time
0.000...1800.000s
0.005s
Displays the expected operating time when a fault occurs. When IDMT
mode is used, the expected operating time depends on the measured
voltage value. If the measured voltage changes during a fault, the
expected operating time changes accordingly.
Time
remaining
to trip
-1800.000...1800.000s 0.005s
When the function has detected a fault and counts down time towards a
trip, this displays how much time is left before tripping occurs.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
144
© Arcteq Relays Ltd
IM00021