Name
Range
Step Default Protection
functions
Description
Safe stall
time hot
0.1…600.0s
0.1s
15.0s
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor
start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 50M)
The safe stall time when the motor is hot. This setting value is
used for the hot thermal stall curve selection in automatic control.
This parameter is also used in the motor start-up and the number
of starts calculations.
Starts
when
cold
1…100
1
3
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
The number of allowed starts per x hours for a cold motor.
Starts
when
hot
1…100
1
2
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
The number of allowed starts per x hours for a hot motor.
Starts in
hours
1…100h
1h
1h
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
The number of hours when the parameters of the number of
allowed starts (hot and cold) apply.
Min time
betw.
starts
0.1…600.0s
0.1s
20.0s
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
The minimum time between starts or start attempts.
Table. 5.4.19 - 167. Output signals of the N> function.
Name
Range Step Default
Description
N> Alarm
on
0: Not
active
1:
Active
1
0
Alarm output of the function. This signal activates when there is one (1) start
available for the motor.
N> Inhibit
on
0: Not
active
1:
Active
1
0
Inhibit output of the function. This signal activates when all available starts have been
used and the motor is not allowed to start before the starts counter has one (1) or
more starts available.
N>
BLOCKED
0: Not
active
1:
Active
1
0
Blocked output of the function. This signal activates when the function is activated
but is blocked from operating normally.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
205