Motor Protector Series Operating Instruction 

(V1.0)

 

NA704L

NA708L

NA712L

 

 

 Main Functions 

  Current  display:

 

display three average current, press key to display A

B

C phase current 

respectively.

 

 

  Underload  protecting:

 

when three phase  average current lower then  setting  current, circuit 

protects and load opens.   

 Overload protecting:

 

when three phase average current exceed rated current, circuit protects and 

load opens.   

 Deficient-phase protecting:

 w

hen testing deficient-phase or three phase current unbalance, circuit 

protects and load opens. 

 Auto reset:

 

when circuit protects and load opens, can set “reset automatically” degree and time, 

after some time, switch on load again, if circuit still has malfunction, try several times, then must reset 
manually. 

 

 

¤

 

Main Technique Index 

 Current display range: 

0

50A (NA704L),0

100A (NA708L), 

0

120A (NA712L),precision ±2% 

 Rating current range: 

   

Sort 

Min(A) 

Max(A) 

NA704L 

1.0 

40.0 

NA708L 

80 

NA712L 

120 

 Underload protect action time: 

  0.5

30s (adjustable) 

 Overload protect action time: 

  0.5

30s (adjustable) 

 deficient-phase protect action time:

 0.5

30s (adjustable) 

 Power supply:

 AC 220V±10%

 

 Operating environment: 

  temperature -10

℃~

45

℃,

humidity

≤85%

 Relay contact capability: 

2A/250VAC (pure resistive load) 

 Executive standard: 

  Q/320585 XYK 03 

 

 Operating Guide 

 

The meaning of the LED

 

LED 

light 

flash 

 

phase A 

Display the current of phase A 

A

B

C  LED no light means 

display three phase average 
current 

phase B 

Display the current of phase B 

phase C 

Display the current of phase C 

Alarm 

Circuit protecting,    Load 

opens 

Circuit protects ever, but 

already reset automatically 

 

 

The meaning of the nixietube display

 

In normal, controller displays three phase average current(unit: A), press “SEL

”, then display 

A

B

C phase current respectively. In the alarm state, it displays alarm code. 

Alarm codes: 

Code 

Meaning 

Explanation 

OL. 

overflow 

Current exceed measure range

NA704L  measure range 50A

NA708L measure range 100A, NA712L measure range 140A

 

LAC 

underload 

Load current lower than setting current 

OVL 

overload 

Load current exceed rated current 

PHA 

deficient-phase 

Deficient-phase or three phase current unbalance 

 How to display A

B

C phase current? 

    

  Press “SEL

”then display A

B

C phase current respectively, the correspond LED lights. If 

A

B

C three LED is unlighted,    mean that controller display three average current. 

 How to reset from the alarm state? 

    

  When overload or deficient-phase  protection  occurs, alarm LED lights, and  protection  circuit 

activates, the load opens, finally the state of open locks. You can set “reset automatically” degree and time, 
after some time, switch on load again, if circuit still has malfunction, try several times, then must reset 
manually. In any time, if press “RST

”, reset from the alarm state. 

 How to set the parameter? 