The Micro-controller can change the parameter, in order to fit different needs. Using the password can 

enter into the menu, password is “up down up down up up down”, according to this gradation, in normal 
temperature state ,press “

” “

” during 3 seconds, if the password is right, the screen displays “Fxx”, 

“xx” is two numbers, means parameter’s code.

 

    Press “

”or“

”for choosing parameter’s code, press “

”“

” at the same time for confirming, then 

press “

”or“

”in order to changing the parameter, when the parameters have been adjusted ,press “

” 

”to confirm.(after adjusted the parameter ,press“

” “

” to return to “Fxx” synchronously, the 

adjusted parameter is saved.) 
    Another way is that press “

”“

” simultaneously at least 5 seconds, then also enter into parameter 

setting. 

Parameter code is showing below: 

Sort 

Code 

Parameter Name 

Range 

Factory 

Setting 

Unit 

Remark 

Rating 

parameter 

F10 

NA704L 

Underload Current:: NA708L 

NA712L 

1.0 – 40.0 

2 – 80 

2 – 120 

1.0 


 

F11 

NA704L 

Rated Current::    NA708L 

NA712L 

1.0 – 40.0 

2 – 80 

2 – 120 

20.0 

40 

120 

 

F12 

Overload acts time

 

0.5 – 30.0 

3.0 

sec 

 

F13 

Deficient-phase acts time 

0.5 – 30.0 

2.0 

sec 

 

F14 

Underload acts time 

OFF 

1 -- 30 

OFF 

min 

OFFmeans no underload 
function 

Reset 

automatically 

F21 

Reset automatically degree 

0 -- 10 

degree 

0 means no “Auto Reset” 

F22 

Reset automatically time 

1 -- 60 

min 

 

 

F00 

Exit the parameter setting 

   

 

 Basic Operating Principle   

    Current Testing 

Through mutual inductor tests load current, the motor’s three phase wire must be through mutual 

inductor’s three holes. 

    Underload protection 

when three phase  average current lower then  setting  current  (parameter F10), also reach the 

“Underload acts time” (parameter F14), circuit protects and load opens.   

  Overload protection 

When  three  phase  average current  exceeds rated current  (parameter F11), also reach the “Overload 

acts time” (parameter F12), circuit protects and load opens. In order to prevent the motor startup current, 
“Overload acts time” must be longer than motor startup time. 

    Deficient-phase protection 

Testing the load current, When the maximum current of the three phase is double than the minimum, 

controller considers deficient-phase, circuit protects and load opens. But if the load current is less than 
0.5A(NA704L)or 1A

NA708L/712L

, controller don’t test phase, in order to prevent the error action in 

the no load state.   

“Deficient-phase acts time” can be adjustable through parameter F12. 

    Reset automatically 

After circuit protects and load opens, controller can set reset automatically degree  (parameter F21) 

and time (parameter F22). 

 
Wiring Diagram: 

  

  

            

NA704L                       NA708L                      NA712L 

 
Notice

 

1. The earth terminal of the controller should be connected with the earth terminal of the electric 

cabinet reliably

be sure to connect the earth well.   

2. Please use mutual inductor which are supplied by our company. 

 