Restriction
System
Option
Description
Allow Engineer
Enable this feature to ensure that the engineer can only access the system if
the user allows it.
If disabled, ENABLE ENGINEER menu option on keypad is not available.
Note:
Only available if
Security Grade
is ‘Unrestricted’. For Grade 2/3, user
control of engineer access to system is always available.
Allow
Manufacturer
Enable this feature to ensure that the engineer can only access the system if
the user allows it.
If disabled, ENABLE MANUFACTURER menu option on keypad is not
available.
Note:
Only available if
Security Grade
is ‘Unrestricted’. For Grade 2/3, user
control of engineer access to system is always available if user type is
‘Manager’.
SMS
SMS
Authentication
Select one of the following options:
l
PIN Code Only: This is a valid user code.
l
Caller ID Only: This is the phone number (including three-digit country
prefix code) as configured for user SMS control. SMS control will only be
available for configuration by the user when this option is selected.
l
PIN and Caller ID
l
SMS PIN Code Only This is a valid PIN code configured for the user which
is different from the user’s login code. SMS controls will only be available
for configuration by the user when this option is selected.
l
SMS PIN Code & Caller ID.
Policy
Web Only
System Policy
Configure engineer login and tamper reporting behavior for system.
Web Only
Timing Policy
Display system timing policy.
Web Only
Output
Configuration
Click the
Edit
button to configure latch and autoset output settings (see
Configuring system latch and auto set outputs
Web Only
System Alert
Policy
This programming option allows you to restrict the user and engineer’s ability to
restore, Isolate and inhibit alerts. The manner in which the system reacts to
alerts can also be programmed.
Web Only
Zone Alarm
Policy
Select whether particular zone alarms can be restored, inhibited or isolated by
the user and engineer.
Web Only
Zone Tamper
Policy
Select whether particular zone tampers can be restored, inhibited or isolated by
the user and engineer.
Web Only
Keypad Display
Policy
Select events to be displayed on keypads in both Set and Unset modes.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Engineer programming via the browser
© Vanderbilt 2018
260
A6V10276959-d
11.2018