l
Default Command Profile (this does not support audio video verification)
l
Default
FlexC Command User Name
(FlexC) and
Command Password
(FlexC) for
controlling the panel from the RCT (for example, SPC Com XT)
l
Auto Encryption with no password
1. To quickly configure a FlexC connection between a panel and an RCT (for example, SPC Com
XT), go to
Communications > FlexC > FlexC ATS
.
2. Under
Add EN50136-1 ATS
, choose one of the following to display the
ATP Configuration
:
l
Add Single Path ATS
- primary ATP only
l
Add Dual Path ATS
- primary and backup ATPs
l
Add Dual Path Dual Server ATS
- primary and backup ATPs, primary and backup servers
3. Complete the fields on the
ATP Configuration - EN50136 ATS
page shown in the table below.
At a minimum, you must complete the field
RCT URL
or
IP Address
to save. If you do not enter
an
SPT Account Code
, you can commission the panel using the
ATS Registration ID
which is
automatically generated when you save. The RCT operator must enter this
ATS Registration
ID
, for example, in SPC Com XT.
4. Click
Save
. The
ATS Configuration
page displays showing the
ATS Registration ID
and the
configured primary ATP or primary and backup ATPs in the
Event Sequence Table
.
5. On the
ATS Configuration
page, click
Save
to accept the default settings, for example, the
Default Event Profile
, the
Default Command Profile
(including the FlexC
Command User
Name
and FlexC
Command Password
), and
Auto Encryption
with no password. To change
the settings, see
Configuring an EN50136-1 ATS or Custom ATS
6. Click
Back
. The ATS displays in the
Configured ATS
table.
Panel Identification
ATS
Name
Enter the name of the ATS. If you do not enter a value, the ATS name defaults to ATS 1, ATS 2,
etc.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual