Attribute
Description
PIN to
Set/Unset
PIN is required to set and unset the linked area. The card has to be presented before the PIN is
entered.
Unset
outside
(Browser)
Panel/area will unset, when card is presented at entry reader.
Unset
inside
(Browser)
Panel/area will unset, when card is presented at exit reader.
Bypass
alarm
Access is granted if an area is set and the door is an alarm or an entry zone type.
Fullset
outside
(Browser)
Panel/area will fullest, when card is presented twice at entry reader.
Fullset
inside
Panel/area will fullest, when card is presented twice at exit reader.
Force
Fullset
If the user has rights, they can force set from entry reader.
Emergency
Door lock opens if a fire alarm is detected within the assigned area.
Emergency
any
Fire in any area will unlock the door.
Escort
The escort feature enforces privileged card holders to escort other card holders through specific
doors. If this feature is assigned to a door, a card with the “escort right” has to be presented first,
to allow other cardholders without this right to open the door. The time period in which cardholders
are able to present their cards after a card with escort right was presented, can be configured per
door.
Prevent
Passback*
Anti-passback should be enforced on the door. All doors must have entry and exit readers and
must be assigned to a door group.
In this mode, cardholders must use their access card to gain entry into and exit from a defined
door group. If a valid cardholder has presented his access card to enter a door group and not
presented the card to exit it, the cardholder is in breach of the anti-passback rules. Next time the
cardholder attempts to enter the same door group, a hard anti-passback alarm will be raised and
the cardholder will not be permitted entry to the door group.
Soft
Passback*
Anti-passback violations are only logged. All doors must have entry and exit readers and must be
assigned to a door group.
In this mode, cardholders must use their access card to gain entry to and exit from a defined door
group. If a valid cardholder has presented his access card to enter a door group and not presented
the card to exit it, the cardholder is in breach of the anti-passback rules. Next time the cardholder
attempts to enter the same door group, a soft anti-passback alarm will be raised. However, the
cardholder will still be permitted entry to the door group.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Engineer programming via the keypad
© Vanderbilt 2018
151
A6V10276959-d
11.2018