16.13.2 Ethernet Ports
To program the Ethernet port:
1. Scroll to ETHERNET PORT.
2. Press SELECT.
The IP ADDRESS option displays, XXX.XXX.XXX.XXX For single digits, leading zero(s) are
required, for example, 001.
3. Press SELECT and enter the preferred IP address.
When the ENTER key is operated, the system beeps twice and states UPDATED if the IP
address is valid. If the IP address is allocated manually, then this must be unique on the LAN or
VLAN, connected to panel. A value is not entered if the DCHP option is used.
4. Scroll to IP NETMASK.
5. Press SELECT and enter the IP NETMASK format XXX.XXX.XXX.XXX. (For single digits,
leading zero(s) are required, for example, 001.) When the ENTER key is operated, the system
beeps twice and states UPDATED if the IP NETMASK is valid.
6. Scroll to GATEWAY. Note the gateway needs to be programmed for access outside the network
(for use with the Portal).
7. Press SELECT and enter the GATEWAY format XXX.XXX.XXX.XXX. (For single digits, leading
zero(s) are required, for example, 001.) When the ENTER key is operated, the system beeps
twice and states UPDATED if the GATEWAY is valid.
8. Scroll to DHCP. The DHCP is enabled if the LAN has a DHCP server to allocate the IP address.
The IP address is to be enabled manually. Note the gateway needs to be programmed if the
panel needs access outside the network (for Portal service).
9. Press SELECT and enter the GATEWAY format XXX.XXX.XXX.XXX. (For single digits, leading
zero(s) are required, for example, 001.)
When the ENTER key is operated, the system beeps twice and states UPDATED if the
GATEWAY is valid.
The DHCP option is displayed.
10. Toggle between DHCP ENABLED and DISABLED for preferred option.
11. Press SELECT.
16.13.3 Modems
The SPC system supports SPC intelli-modems for communications with analogue lines and mobile
network interfacing for enhanced communications and connectivity. The SPC system must be
configured accordingly.
16.13.3.1 Monitoring the transmission network interface
The SPC Alarm System sends a poll to SPC Com XT, which responds with a poll acknowledge (ACK).
On receipt of a valid poll ACK the SPC Alarm System updates its status to OK and resets its polling
interval timer (depending on the ATP category).
If the SPC Alarm System does not receive a polling ACK within the timeout (depends on ATP
category), the SPC Alarm System updates its status to DOWN.
SPC supports the following transmission interfaces:
l
Ethernet
l
GSM with GPRS enabled
l
PSTN modem.