3. Enter Engineer programming from the keypad and configure the modem (primary or backup) to
answer an incoming call.
4. On the keypad, scroll to
Full Engineer Mode > Comms > Modems
.
5. Select the following settings:
-
Enable Modem:
Set to enabled
-
Type:
Displays the type of modem (PSTN)
-
Country Code:
Select the relevant country code (Ireland, UK, Europe)
-
Answer mode:
Select numbered rings; this tells the modem to wait for a number of rings before
answering the incoming call
-
Modem Rings:
Select the number of rings to allow before answering the call (8 rings max)
6. Create a dial-up connection on the remote PC using the phone number of the telephone line
connected to the PSTN module on the controller. The instructions to do this on Windows XP
operating system are listed below.
On Windows XP:
1. Open the New Connection Wizard by browsing to
Control Panel > Network Connections >
Create New Connection
(in the
Network Tasks
page).
2. On the
Network Connection Type
page, select
Connect to the Internet
.
3. On the
Getting Ready
page, choose
Setup my connection manually
.
4. On the
Internet Connection
page, choose
Connect using Dialup modem
.
5. On the
Connection Name
page, enter the connection name, for example, SPC remote connection.
6. On the
Phone Number to Dial
page, enter the phone number of the PSTN line connected to the
PSTN modem.
7. On the
Connection Availability
page, choose whether this connection is available to all users.
8. On the
Internet Account Information
page, enter the following details:
- Username: SPC
- Password: password (default)
- Confirm Password: password
The
Completing the New Connection Wizard
page is displayed.
9. Click
Finish
to save the Dial-up connection to the PC.
Default code should be changed and noted accordingly as Vanderbilt is unable to retrieve this new
code. Forgotten codes are be remedied only by a factory default of the system, rendering loss of
programming. Programming can be restored if a backup is available.
To activate this dial-up connection:
l
Click the icon located in the
Control Panel > Network Connections
page.
The PC makes a data call to the PSTN line connected to the SPC PSTN module.
The SPC PSTN module answers the incoming data call after the designated number of rings and
establishes an IP link with the remote computer.
The SPC system automatically assigns an IP address to the remote PC.