The keypad buzzer sounds continuously for approximately 2 seconds to indicate that the zone
activation has been detected and the number of zones left to test (displayed on the keypad)
decreases.
4. Continue with the remaining zones on the system until all zones have been tested. If a zone
activation does not get acknowledged by the system, check the wiring of the sensor and/or replace
with another sensor if necessary.
NOTICE: All zones can be included in an Engineer walk test.
16.14.3 Zone Monitor
The Zone Monitor option displays status information on each of the zones on the system.
To view zone status information:
1. Scroll to TEST > ZONE MONITOR.
2. Press SELECT.
3. Scroll to a preferred zone and press SELECT.
The status of the zone and its associated resistance value is displayed.
4. Press NEXT to locate the zone (for example, CONTROLLER 1 = first zone on Controller).
See the table below for correlating status information (valid for Dual EOL resistors).
Zone status
Abbreviation
UNKNOWN
UK
CLOSED
CL
OPEN
OP
SHORT
SH
DISCONNECTED
DI
PULSE
PU
GROSS
GR
MASKED
AM
FAULT
FA
DC SUB
DC
OUT OF BOUNDS
OB
UNSTABLE
US
All zones on a system can be monitored for correct operation by performing a monitoring test.
To perform a zone monitoring test:
1. Scroll to ZONE MONITOR.
2. Press SELECT.
3. Scroll to a preferred zone and press SELECT, or enter the zone number directly.