Hardware Requirements
l
The minimum battery capacity for SPC42xx/43xx/52xx/53xx/63xx is 10Ah/12V. If a 10Ah battery is
used, then the battery is biased to the left of the housing and the bottom flap is bent to meet the
battery.
l
Fit jumper (J12) on the battery selector for 17/10Ah battery use and remove for 7Ah battery.
l
The amount of current from Aux output using a 10Ah battery for SPC42xx/SPC52xx is:
COMMS
NONE (mA)
PSTN (mA)
GSM (mA)
PSTN+GSM (mA)
Standby time
12 h
568
543
438
413
24h
214
189
84
59
30 h
143
118
13
N/A
60h
2
N/A
N/A
N/A
l
The amount of current from Aux output using a 10Ah battery for SPC43xx/SPC53xx/ SPC63xx is:
COMMS
NONE (mA)
PSTN (mA)
GSM (mA)
PSTN+GSM (mA)
Standby time
12 h
538
513
408
383
24 h
184
159
54
29
30 h
113
88
N/A
N/A
60 h
N/A
N/A
N/A
N/A
3.5 PD 6662:2010 Conformance Guidelines
This document contains all the criteria for the installation, and commissioning and maintenance of the SPC
System to enable it to conform to the PD 6662:2010 Standard.
3.5.1 Product scope
The scope of this document is aimed at the following components of the SPC system:
SPC4320.320-L1 Grade 2 Controller
SPC5320.320-L1 Grade 2 Controller
SPC5330.320-L1 Grade 3 Controller
SPC5350.320-L1 Grade 3 Controller
SPC6330.320-L1 Grade 3 Controller
SPC6350.320-L1 Grade 3 Controller
SPCK420/421.100 LCD Keypad
SPCE452.100 Expander, 8 Relay Outputs
SPCE652.100 Expander, 8 Inputs/2 Outputs
SPCP332.300 Smart PSU with I/O Expander
SPCP355.300 Smart PSU with 8 Inputs/2 Outputs Expander
SPCP333.300 Smart PSU with I/O Expander
SPCN110.000 PSTN Module
SPCN320.000 GSM Module
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Directives and standards
© Vanderbilt 2018
23
A6V10276959-d
11.2018