
Output Type
Description
Smoke
This output turns on momentarily( 3 seconds) when a user unsets the system; it can be used to reset
smoke detectors.
The output will also activate when the zone is restored.
When using the zone to reset latched smoke detectors the first code entry will not activate the
smoke output but will silence bells, on the next code entry if the fire zone is in the open state the
smoke output will activate momentarily. This process is repeatable until the fire zone is closed.
Walk Test*
This output turns on momentarily when a walk test is operational and a zone becomes active. This
output can be used, for example, to activate functional tests of connected detectors (if available).
Auto Set
This output turns on if the Auto Set feature has been activated on the system.
User Duress
This output turns on if a user duress state has been activated (PIN code + 1 has been entered on the
keypad).
PIR Masked
This output turns on if there are any masked PIR zones on the system. It generates a fault output on
the keypad led.
This output is latched so it will remain active until restored by a level 2 user.
PIR Masking is logged by default. The number of log entries do not exceed 8 between arming
periods.
Zone Omitted
This output turns on if there are any inhibited, isolated, or walk test zones on the system.
Fail to
Communicate
This output turns on if there is a failure to communicate to the central station.
Man Down
Test
This output turns on a ‘Man Down’ wireless device which is activated during a ‘Man Down’ test.
Unset
This output is activated if the system is in Unset mode.
Alarm Abort
This output activates if an alarm abort event occurs, that is, when a valid user code is entered via the
keypad after a confirmed or unconfirmed alarm. It is used, for example, with external dialers (SIA,
CID, FF).
Seismic Test
This output is used to activate a manual or automatic test on a seismic zone. Seismic sensors have
a small vibrator that will be attached to the same wall as the sensor and is wired to an output on the
panel or one of its expanders. During the test, the panel waits up to 30 seconds for the seismic zone
to open. If it does not open, the test fails. If it opens within 30 seconds the panel then waits for the
zone to close within 10 seconds. If that doesn’t happen, the test fails. The panel then waits a further
2 seconds before reporting the test result. The result of the test, either manual or automatic, is stored
in the system event log.
Local Alarm
This output activates on a local intrusion alarm.
RF Output
This output activates when a Fob or WPA1 button is pressed.
Modem 1 Line
Fault
This output activates when there is a line fault on the primary modem.
Modem 1
Failure
This output activates when the primary modem fails.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Engineer programming via the keypad
© Vanderbilt 2018
155
A6V10276959-d
11.2018