Number
Description
1
Tamper
2
Alarm
3
EOL 4k7
4
EOL 4k7
Anti-Masking PIR configuration
Number
Description
1
Tamper
2
Alarm
3
EOL 4k7
4
Fault
5
EOL 2K2
6
EOL 4k7
The following table shows the resistance ranges associated with each configuration.
Single EOLs
EOL Type
Quiescent
Alarm
Min
Nom
Max
Min
Nom
Max
NONE
0Ω
(-100%)
150Ω
300Ω
(+100%)
300Ω
(+100%)
N/A
Infinite
SINGLE_1K
700Ω
(-30%)
1kΩ
1.3kΩ
(+30%)
23kΩ
N/A
Infinite
SINGLE_1K5
1.1kΩ
(-27%)
1.5kΩ
2.1kΩ
(+40%)
23kΩ
N/A
Infinite
SINGLE_2K2
1.6kΩ
(-28%)
2.2kΩ
2.9kΩ
(+32%)
23kΩ
N/A
Infinite
SINGLE_4K7
3.1kΩ
(-22%)
4.7kΩ
6.3kΩ
(+24%)
23kΩ
N/A
Infinite
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Wiring the system
© Vanderbilt 2018
86
A6V10276959-d