Commissioning an inverter
Operation manual POSIDYN® SDS 5000
ID 442289.06
WE
KEEP
THINGS
MOVING
23
3
The following Figure 3 1 shows which state changes are possible. The table below shows which conditions
apply.
Fig. 3-1: Standard device state machine
Nicht Einschaltbereit
Einschaltsperre
Einschaltbereit
Eingeschaltet
Betrieb freigegeben
Schnellhalt aktiv
Störung
Störungsreaktion aktiv
0
2
1
3
4
5
6
9
7
8
11
12
14
13
15
16
10
Not ready for switchon
Fault reaction active
Fault
Quick stop active
Switchon disable
Ready for switchon
Switched on
Operation enabled
Change of state
Conditions
0
Device start-up
Not ready to switch on Control unit power supply turned on.
1
Not ready to switch on
switch on
disable
Self test without errors and initialization completed.
2
Switch on disable
ready to switch on
•
Enable on low level (
E19
bit 0 = 0 or
A300
= 0) or for
initial start-up autostart active (
A34
)
•
DC link charged (
E03
)
•
Option ASP 5001 (Safe Torque Off) is not active (
E67
).
•
Axis activated (
E84
)
•
An IGB motion bus is not configured (configuration
wizard, step 6, check box) or
•
No IGB motion bus is configured and either the IGB has
reached the state
3:IGB motion bus
(
A155
) or IGB
exception mode is activated (
A124
) or local mode is
activated.
3
Ready to switch on
switched on
Enable on high level (
E19
bit 0 = 1 and
A300
= 1).
4
Switched on
operation enabled
Enable on high level (
E19
bit 0 = 1 and
A300
= 1).
5
Switched on
ready to switch on
Enable on low level (
E19
bit 0 = 0 or
A300
= 0).