Diagnosis
O
peration
man
ual
POSIDYN
®
SDS
5000
16
7
ID 442
289
.06
WE KEEP THINGS MOVING
13
7:EtherCAT-DcSYN
If the inverter is synchronized to
EtherCAT by means of the Distributed
Clock, the "SYNC 0" synchronization
signal is checked by a watchdog. If this
SYNC 0 signal remains for a certain
time (that cannot be parameterized),
this cause is triggered. This cause can
only be triggered for EtherCAT with
synchronization by the Distributed
Clock.
•
Check the controller.
•
Make sure that the wiring is in
accordance with electromagnetic
interference regulations.
•
Replace the ECS 5000.
•
Please contact our service
department, see section 1.4 Further
Switch the device off/on or
programmed acknowledgement.
Note that an action must also
occur in the controller or the
EtherCAT master for complete
acknowledgement.
8:IGB µC failure
The microcontroller for the IGB
communication has failed.
•
Check the wiring for EM-compliant
design.
•
The inverter must be sent in for
repair. Please contact our service
department, see section 1.4 Further
Switch the device off/on or
programmed acknowledgement
9:IGB Lost Frame
IGB motion bus: The subscriber has
detected the loss of min. 2 consecutive
data frames (double error). This cause
can only occur when the IGB state =
3:Motion bus
and the motor is powered.
•
Make sure that all inverters in the
IGB network are switched on.
•
Make sure that all connection
cables are plugged in.
Switch the device off/on or
programmed acknowledgement
10:IGB P. LostFr
IGB motion bus: A different subscriber
has detected a double error and
reported this via
A163
. As a result, this
inverter is also faulty with this cause.
This cause can only occur when the IGB
state =
3:Motion bus
and the motor is
powered.
Switch the device off/on or
programmed acknowledgement
Cause
Description
Measure
Acknowledgement