Diagnosis
O
peration
man
ual
POSIDYN
®
SDS
5000
16
9
ID 442
289
.06
WE KEEP THINGS MOVING
13
13.3.18 55:OptionBoard
Resolution
Level
Response
Fault counter
Error when operating with option board.
Malfunction
The parameterized malfunction reaction in the
A29
parameter.
Z55
Cause
Description
Measure
Acknowledgement
1:CAN5000Failure
CAN 5000 was detected, installed and
failed.
•
Uninstall the option, check the
contacts and reinstall the option.
•
Replace the option.
Switch the device on/off or
programmed acknowledgement
2:DP5000Failure
DP 5000 was detected, installed and
failed.
3:REA5000Failure
REA 5000 was detected, installed and
failed.
4:SEA5000failure
SEA 5000 was detected, installed and
failed.
5:XEA5000Failure
XEA 5000 or XEA 5001 was detected,
installed and failed.
6:InkSim-Init
Incremental encoder simulation on XEA
could not be initialized. The motor may
have rotated during initialization.
7:wrongOption
incorrect or missing option board
(see
E54/E58
with
E68/E69
)
•
Install the projected option.
•
Adjust the projection.
Switch device off/on
8:LEA5000failure
LEA 5000 was detected, installed and
failed.
•
Uninstall the option, check the
contacts and reinstall the option.
•
Replace the option.
Switch the device on/off or
programmed acknowledgement
9:ECS5000failure
ECS 5000 was detected, installed and
failed.
•
Uninstall the option, check the
contacts and reinstall the option.
•
Replace the option.
Switch the device on/off or
programmed acknowledgement
10:24Vfailure
Failure of 24V supply for XEA 5001 or
LEA 5000.
Check and, if necessary, correct the
24V supply of the option.
Switch device off/on