13.3.2
32:Short/gr.int
13.3.3
33:Overcurrent
Resolution
Level
Response
Fault counter
An internal test is performed when the controller
part power supply is switched on. An existing
short-circuit causes a malfunction. A requirement
for triggering this event is for the supply voltage
to already be present when starting the device.
Malfunction
The inverter cannot be enabled.
Z32
Possible cause
Test
Measure
Acknowledgement
There is an internal device
fault.
—
Please contact our service department,
see section 1.4 Further support
Switch the device on/off or
programmed
acknowledgement
Triggering
Level
Response
Fault counter
The total motor current exceeds the permitted
maximum value.
Fault
The motor always coasts except when U30 Emergency
stop is activated. Any existing brakes are engaged if they
were not released via
F100
independent of the device
controller.
Z33
Possible cause
Test
Measure
Acknowledgement
Acceleration times too
short.
Extend the ramps.
Apply this setting for operation.
Switch the device off/on or
programmed
acknowledgement
Incorrectly set torque limits
in the
C03
and
C05
parameters.
Set smaller values in
C03
and
C05
.
Apply this setting for operation.