Diagnosis
Operation
manual
POSIDYN®
SDS
5000
17
2
ID 44
22
8
9
.0
6
WE KEEP THINGS MOVING
13
13.3.20 57:Runtime usage
13.3.21 58:Grounded
Triggering
Level
Response
Fault counter
The cycle time of a real time cycle was
exceeded.
Fault
The parameterized fault reaction in the
A29
parameter.
Z57
Cause
Description
Measure
Acknowledgement
2:RT2
Cycle time of real time task 2 exceeded
(1 ms).
Replace the inverter.
Switch the device off/on or
programmed acknowledgement
3:RT3
Cycle time of real time task 3 exceeded
(technology task).
Set a higher cycle time in A150.
4:RT4
Cycle time of real time task 4 exceeded
(32 ms).
5:RT5
Cycle time of real time task 5 exceeded
(256 ms)
Resolution
Level
Response
Fault counter
Unbalanced motor currents were detected.
This involves a hardware from the power
stage for MDS 5000 size 3 or SDS 5000 size
3.
Malfunction
The motor continues to coast. Any existing brakes are
engaged if they were not released via
F100
independent
of the device controller. The brake chopper is switched
off as long as the malfunction is present.
Z58
Possible cause
Test
Measure
Acknowledgement
Ground fault in motor
Check the motor.
Replace the motor.
Switch the device on/off or
programmed acknowledgement
Fault in motor cable
Check the cable.
Replace the cable
Connection fault
Check the connection, e.g. whether V or
W is connected to PE at X20 U.
Correct the connection.