Diagnosis
O
peration
man
ual
POSIDYN
®
SDS
5000
16
3
ID 442
289
.06
WE KEEP THINGS MOVING
13
13.3.14 45:oTempMot. i2t
13.3.15 46:Low voltage
Resolution
Level
Response
Fault counter
The i
2
t model for the motor
reaches 100% load.
Parameterized as inactive,
message or warning in
U10
and
U11
.
The parameterized malfunction reaction in the
A29
parameter.
Z45
Possible cause
Test
Measure
Acknowledgement
The motor is overloaded
Check whether the operating conditions
have caused the motor to overheat
(load state, ambient temperature of the
motor, etc.).
•
Take measures to meet the
requirements for the operating
conditions.
•
Rectify any existing blockages.
•
If necessary, correct the drive
design.
Switch the device off/on or
programmed acknowledgement.
Resolution
Level
Response
Fault counter
A problem with the supply
voltage or DC link voltage was
detected.
•
Cause 1: Parameterized in
U00
and
U01
•
Cause 2: Warning with 10 s
warning time
•
Cause 3: Malfunction
The parameterized malfunction reaction in the
A29
parameter for cause 1 and 2. For cause 3, the motor
always coasts except when
U30 Emergency stop
is
activated.
Z46