PART 2: CX-Server PLC Tools
CHAPTER 10 – Data Link Editor
OMRON
CX-Server PLC Tools_Page 98
Starting and Stopping Data Links (Including Status Displays)
Before performing the operations described below, connect online to a node where the data link table has been
transferred. As long as the data link table is stored there, data link starting and stopping can be executed from
any node.
Note:
When starting data links with manual setup, the data link mode for the startup node
must be set to manual.
Starting Data Links
1 Select
Data Link | Setup
from the CX-Net.
The Data Link Setup dialog box will be displayed. (For local network only, i.e., when network address is 0.)
Clicking on this down arrow will
display the Communications
Units mounted to the PLC, as
shown below.
2 Select
Controller Link
or
SYSMAC LINK
, and then click the
OK
button.
Either the Datalink Component (Controller Link) or Datalink Component (SYSMAC LINK) window will be
displayed.
Summary of Contents for Sysmac WS02-CXPC1-EV3
Page 1: ...Cat No W414 E1 01 SYSMAC...
Page 2: ......
Page 3: ...SYSMAC WS02 CXPC1 EV3 CX Programmer Ver 3 1 Operation Manual Revised November 2002...
Page 4: ......
Page 6: ......
Page 7: ...PART1 CX Programmer...
Page 8: ......
Page 24: ......
Page 34: ......
Page 106: ......
Page 130: ......
Page 131: ...PART 2 CX Server PLC Tools...
Page 132: ......
Page 136: ......
Page 158: ......
Page 168: ......
Page 194: ......
Page 206: ......
Page 250: ......
Page 298: ......
Page 304: ......
Page 305: ...PART 3 CX Server Runtime...
Page 306: ......
Page 310: ......
Page 338: ......
Page 344: ......
Page 378: ......
Page 384: ......
Page 388: ......