PART 2: CX-Server PLC Tools
CHAPTER 10 – Data Link Editor
OMRON
CX-Server PLC Tools_Page 86
Procedure Using Setup Example
Set Area 1 for each node, based on the data link setup example in the example system configuration.
Note:
The receive size and reception offset can only be set for Controller Link, and not for
SYSMAC LINK.
Setting Node Address 01
1
Select node address 01 from the node address list on the left. Node 01 will be highlighted.
Select node address 01 as the object to be edited.
The data link data for the selected node
address is displayed here.
The data link table for node address 01, the node to be edited, is displayed as a list in the Node Editing window
on the right.
Receive area from
remote nodes
Indicates the node refresh
sequence. (In this example,
for node address 01, no
change is required.)
Sends 30 words from the local node (node address
01), starting with CIO 01000 (i.e., CIO 01000 to CIO
01029).
Receives 30 words from node 02, starting with
CIO 01230 (i.e., CIO 01230 to CIO 01259) into
the local node area starting with CIO 01030
(i.e., CIO 01030 to CIO 01059).
Receives 40 words from node 03, starting with
CIO 00350 (i.e., CIO 00350 to CIO 00389) into
the local node area starting with CIO 01060
(i.e., CIO 01060 to CIO 01099).
Local node send area
Reference:
With node address 01, the node refresh sequence matches the default (order of
addresses), so no change is required.
With node address 01, the size and offset are both automatically displayed as the
defaults, so no changes are required.
The size and offset can be set.
Automatically displayed.
2. With node address 01, the node refresh sequence matches the default (order of addresses), so no change is
required.
With node address 01, the size and offset are both automatically displayed as the defaults, so no changes
are required.
Settings for area 2 are made using the same method.
Summary of Contents for Sysmac WS02-CXPC1-EV3
Page 1: ...Cat No W414 E1 01 SYSMAC...
Page 2: ......
Page 3: ...SYSMAC WS02 CXPC1 EV3 CX Programmer Ver 3 1 Operation Manual Revised November 2002...
Page 4: ......
Page 6: ......
Page 7: ...PART1 CX Programmer...
Page 8: ......
Page 24: ......
Page 34: ......
Page 106: ......
Page 130: ......
Page 131: ...PART 2 CX Server PLC Tools...
Page 132: ......
Page 136: ......
Page 158: ......
Page 168: ......
Page 194: ......
Page 206: ......
Page 250: ......
Page 298: ......
Page 304: ......
Page 305: ...PART 3 CX Server Runtime...
Page 306: ......
Page 310: ......
Page 338: ......
Page 344: ......
Page 378: ......
Page 384: ......
Page 388: ......